XLdp Differential Pressure Transmitter
Part #: XL3MB242STP25IWL
$906.32
Ashcroft Pressure Transducer, .25% F.S. accuracy, 1/4″” barbed connection, 4-20 mA output, Screw termination, 0 – 0.25″” WC bidirectional range, NIST tracable calibration report.
The Ashcroft® XLdp is a variable capacitance sensor within a glass-clad silicon chip. The patented Si-Glas™ technology combines the inherent high sensitivity of a variable capacitance transducer with the repeatability of a micro-machined, ultra-thin silicon diaphragm.
Part #: XL3MB242STP25IWL
Datasheet: https://nesentrol.com/datasheets/XLDPDataSheet.pdf
• Certified 0.25% and 0.5% accuracy
• 0.1˝-50˝-H2O pressure ranges
• CE approved
• High overpressure protection
• NEMA 2 stainless steel construction
• Three output signals available
• Easy installation
• On-board voltage regulation allows use of lower cost, non-precise, unregulated power supply
• 9 point NIST Traceable Calibration Certificate
- Reference Temperature: 70°F ±2°F (21°C ±1°C)
- Accuracy Class (Span): 0.25% 0.50%
- Non-linearity
- Best fit straight line (BFSL) ±0.15% ±0.30%
- Hysteresis ±0.02% ±0.02%
- Non-repeatability ±0.03% ±0.05%
- Stability – Max. Change (Span/year): ±0.25 %
- Standard Ranges (Inches W.C.)
- Unidirectional Ranges:
Differential or Gauge
0/0.1 0/1.0 0/3.0 0/25.0
0/0.25 0/1.5 0/5.0 0/50.0
0/0.5 0/2.0 0/10.0 0/100.0
0/0.75 0/2.5 0/15.0 - Bidirectional Ranges:
Compound
±0.05 ±1.0 ±5.0 ±100.0
±0.1 ±2.0 ±10.0
±0.25 ±2.5 ±25.0
±0.5 ±3.0 ±50.0
- Unidirectional Ranges:
- Custom Ranges: Special range calibrations
- Standard Response Time: 250msec
- HVAC
- Fume Hood Control
- Lab/Clean/Hospital Room Pressurization
- Medical Lung Function or Breathing Equipment
- Fan Tracking
- Filter Monitoring
- Very Low Velocity Measurements